The FieldServer can emulate both a Client and a Server simultaneously on the same ethernet port. There are various register mapping models being followed by various vendors. To cover all these models FieldServer uses the following three Models. Note 1: If vendor document shows addresses in extended Modicon i. Note 2: The purpose of providing 3 different ways of addressing the Modbus registers is to allow the user to choose the addressing system most compatible with the address list being used.

The Gateways are capable of being used as port expanders and can emulate either a Server or Client. The information that follows describes how to expand upon the factory defaults provided in theconfiguration files included with the FieldServer. Depending on what hardware you require, the specifications will contain different options.

See images below for Port Support and product code check. Modbus does not provide a method for transporting large or Floating Point numbers or a mechanism for scaling analog values. A 16 bit word can only contain values in the range Only whole numbers are permitted. To work around this many server device manufacturers use multipliers and document them in their manuals.

For example, to report a temperature of This scaling is achieved by adopting a convention between the client and the server. MK10 values — Two consecutive words are used. Floating Point Numbers — Two consecutive words are used and a scheme.

These schemes are conventions and not all servers or clients support them. The protocol does not identify these big numbers. Only the vendor docs do. What we mean by this is — if you look at the byte stream in a Modbus message there is no way of telling whether you are looking at two consecutive 16 bit words, or two consecutive words that should be interpreted as floating point, long or MK10 formats.

Because of this you always have to look to the vendor docs. If you are reading the documentation for sensor blocks, valves, and other devices, you must keep in mind that some vendors may document their hardware in different ways. According to the Modbus standard, addresses are simply integers from 0 to 65, with the different address ranges being referred to as coils, holding registers, etc. However, some vendors will document their hardware using numerical prefixes which are not actually part of the Modbus address.

This originated from some models of PLCs which used the Modbus communications protocol, and which also used numerical prefixes in their internal data table. However, it is important to remember that these numerical prefixes are documentation methods and are not part of what the Modbus protocol itself sends as part of the messages. A difference in documentation methods does not affect the compatibility of the protocol itself. These prefixes are they mentioned anywhere in the Modbus standard, but the following shows how they are typically used in documentation based on this older convention:.

In addition to numerical prefixes, some documentation will refer to protocol addresses addresses start at 0 , while other documentation will refer to data model addresses addresses start at 1. That is, the first holding register may be 0 or 1 or versus using prefixes. However, this has no bearing on what gets sent over the wire as a Modbus message. Common Binary Protocol. The 2 bytes are the humand readable form of the single hex byte.

Additional drivers are available at extra cost. QuickServer is ready to configure for the specific application. All necessary instructions and software are included with QuickServer.

If the user prefers the unit to be pre-configured prior to delivery, FieldServer offers a custom configuration service. Contact Us. Please help us improve Stack Overflow. Take our short survey. Stack Overflow for Teams — Collaborate and share knowledge with a private group.

Create a free Team What is Teams? Collectives on Stack Overflow. Learn more. Asked 4 years, 4 months ago. Active 2 years, 7 months ago. Viewed times. I hope someone can take some time to clear my doubts on this. Will really appreciate it. Thank you. SunnyBoiz SunnyBoiz 2 2 silver badges 13 13 bronze badges. Add a comment.